22-0375 rev1.1 Monitor ISM/xL™ Hardware Guide 37
(+)12V
(-)0V
Data B
Data A
1432
1432
56
132 1432
1432
(+)12V
(-)0V
Data A
Data B
N. O.
Com.
N. C.
Com.
N. O.
Common
Common
(+)5/12VDC
Green LED
Red LED
Ground 0V
This Module Bus
connector is for
connecting a
Service LCD
Keypad Module
black
yellow
red
green
132 1212
N. O.
Com.
N. C.
Com.
N. O.
Common
Bypass
Fire Bypass
Common
(+)5/12VDC
Green LED
Red LED
Reader 1 Data 1
Ground 0V
Reader 1 Data 0
Panic Input
1432
56
132 1432132
12
12
Reader 2 Data 0
Reader 2 Data 1
XXXXX
1
st
Elev Data In
2 Elevator
Module
Self resetting
0.5A fuse.
Low Voltage
LED
Processor OK LED
(normal = slow flash)
Unlock Relay
2 LED
Auxiliary Relay 2 LED
Module Bus communications
indicator LED
Auxiliary
Relay 1 LED
Unlock Relay
1 LED
Reader
Reader
Aux
Rly 2
Aux
Rly 1
Unlock
Rly 1
Unlock
Rly 2
2
nd
Elev Data In
Not Used
Not Used
Bypass
Fire Bypass
Panic Input
Module Bus
5V 12V
Reader Voltage
Jumper
5V 12V
Reader Voltage
Jumper
P/N 650-9017
5 digit serial
number to program
in Module
Programming
red
orange
white
green
black
READER
for
Elevator
Module’s
first
elevator
brown not used
13
2
13
2
1214
3
2
5
1
2
13
2
RLY1 RLY2
(+)
(-)
DATA
DATA
DATA0
DATA1
Elevator
Relay Board
Aux
12VDC
(+
)
P/N 650-9035
Cutaway view
Earth
Common
Green LED
Reader 1/2 Data 1
Reader 1/2 Data 0
Elev1/2 Data 0
Elev 1/2 Data In
Bypass
Panic In
0V Neg
(-)
(+)
12VDC
Ground 0V
Common
Bypass
Fire Bypass
Common
Tamper Output
Green LED
Reader 1/2 Data 1
Reader 1/2 Data 0
Panic Out
Elev 1/2 Data 0
Elev 1/2 Data 1
Elev 1/2 Data In
12VDC
12VDC
Ground 0V
P/N 641-9036
121212
321432
1
4
32
1
12
12
12
32
132145632145 32145
(-)
(+)
(+) (-)
Elev1/2 Data 1
(+) 5 / 12 VDC
Spare
Common
TB1
TB10
TB4
TB9 TB7 TB3 TB2
TB13
TB14
TB11
TB12
TB16
TB15
0V Neg
0V Neg
Fire Bypass
RS485 Reader
Connections for
reader runs over 500
ft.
See following
“Wiegand to RS485
Interface Board”
Reader Voltage
Jumper
Module Bus
connection
from the
motherboard
or paralleling
to another
Module
Power
Supply
(+) ( )
Power
Supply
(+) ( )
Relay and
Isolator board
cabinet 12VDC
power supply.
Module Bus
Elevator
Module
12VDC
Power
Supply must
also be
connected to
the Elevator
Module side
of its Isolator
boards.
Elevator
Module
Elevator
side
Elevator
Module
side
Elevator
Isolator
Board
( )
Aux
12VDC
Reader cable shield. Connect
to control unit ground lug.
Elevator Isolators and Relay boards do not have a 5 digit
serial # to program in Module Programming.
Parallel connections to next Elevator Relay board(s)
Power to next Elevator Relay board(s) in this cabinet only. NOTE: If more elevator
relay boards are added in additional expansion cabinets with their own power
supply - ALL RELAY BOARD’S POWER SUPPLY NEGATIVES MUST HAVE A
COMMON CONNECTION.
Fire Bypass is not intended for
"Life/Safety" applications.
2
nd
Elev Data 0
2
nd
Elev Data 1
1
st
Elev Data 0
1
st
Elev Data 1
ELEVATOR MODULE and ISOLATOR BOARD (1
st
elevator connected to 2 Elevator Module)
First Elevator
Connections
to 2 Elevator
Module
Normal RS485
Waterpipe ground input when a
cabinet ground lug is not available.
If quad cable is used, use all four
wires. Terminate two wires in #1
and two wires in #2, for
convenience.
5V 12V
Ground
Earth Ground
Tamper Output
Tamper Output
Elevator Module
current rating =
180mA.
maximum.
Elevator
Isolator Board
current rating:
Elevator
Module
Connections
side =
100mA.
Elevator
Connections
side = 130mA
Plus add all
reader’s
current rating.
12
Tamper
Switch
Input
Not Jumper PINs.
Do not short.
Connect current
protected LED to
remote “Processor
OK LED”.
Not Jumper PINs.
Do not short.
Connect current
protected LED to
remote “LED
Always on When
Power OK”.