NX-8V2 Control Panel Installation Instructions Introduction This is the NX-8V2-Control Panel Installation Instructions. Installations should only be
ANSI/SIA CP-01 requirements CP-01 feature descriptions and specifications are listed in Table 9 below. The following are requirements for compliance w
NX-8V2 Control Panel Installation Instructions 11 CP-O1 feature description Feature description as shown in manual Program location Seg/opt Default
Terminal Description KP POS Connect to the POS terminal on the keypads and the expanders. Individually, this terminal is limited to 1 amp. Combined,
Select the module to program Since all modules connected to the NX-8V2 are programmed through the keypad, the module you are programming should be the
Location 0 - Phone 1 Location 0 has 20 segments of numerical data. Use this location to program phone 1. The default for each segment is 14. • To pro
Segment 2 - Phone 1 backup control Program the backup control for phone 1. The default is 0. • Program a 0 in segment 2 to cause the NX-8V2 to make t
Zone type Description Zone type Description 2. 24-hour audible. This zone creates an instant yelping siren alarm regardless of the armed state of th
UL294 Access control system units UL365 Police station connected burglar alarms UL609, CAN/ULC-S303-M91 Mercantile, police station connect with basic
protected area, is acceptable, provided it is rated for outside service and alarm conditions are transmitted to: a) The dispatch location of the law e
NX-8V2 Control Panel Installation Instructions 9 • The DACT shall be enabled for all commercial burglary applications. UL requires that an alarm pan